Deaktivieren | With this option the outputs of the block are no longer updated. This option can be used to temporarily disable blocks for diagnostic purposes. |
Send
cyclically |
Outputs are updated cyclically. If
variables are linked at the outputs, they are updated cyclically. If
the linked variable is changed e.g. from the visualization, the
block resets it after the set time. A practical example would be the
time switch: Normally, the output (e.g. an outdoor light) is only
updated at the switching time, after which the outdoor light can
also be switched on and off via the visualisation. If you set this
parameter to 600 seconds, for example, you can switch on the light
and after 10 minutes the clock would switch back to the original
value. |
Comment |
General comment, this is displayed in
the middle of the function module |
Update
outputs on startup. |
With this parameter the outputs are
forcibly updated at start and telegrams and the function block is
called at all events. For pure KNX projects it may be useful to switch off this parameter to avoid duplicate telegrams. Important: This parameter should always be active for projects with IO modules or critical outputs. |
Parameter Seite
|
||
Name |
Name of the page |
|
Start
delay |
This can be used to set a start
delay, which causes the function blocks to be processed internally,
but no outputs are written. These are then only updated when the
next change is made. This function is useful if the status of the
system is not to be changed when program changes are made, for
example, if work is still being carried out in a building and no
lights or blinds are to be activated during the changes. Important: This parameter should always be set to 0 for projects with IO modules or critical outputs. |
|
Deactivate | This parameter deactivates all function modules on this page. | |
Deactivate Address | An address can be entered here to dynamically activate or deactivate all function modules on this page (1=deactivate). |