Block Air Conditioner / Fan Coil| This
function block controls a fan coil unit or a split air conditioner. It
receives the control value of a controller at input SG and derives the
fan speed from it, operates the valves in the correct order and
provides the protective functions of the unit: minimum run time and
minimum idle time, valve lead time, fan overrun, changeover lock
between heating and cooling, condensate monitor, frost protection and
window contact. The control value is usually supplied by the Block Room Controller block. If the parameter "Fan coil connected" is set there, the controller gets four additional outputs SG, KU, SH and BA that match the first four inputs of this block exactly - same abbreviations, same order, so they can be wired straight across. The air conditioner is then operated in the Block Room Controller control element; this block has no control element of its own. The block also works without a room controller. In that case the control value comes from another source, or the unit is only switched by hand through input SH. |
| The fan
speed results from the control value at input SG. A threshold in
percent is set for each speed; the highest threshold that is exceeded
determines the speed. Typical values are 10, 40 and 70 %. The hysteresis only takes effect when switching back down: switching up happens immediately as soon as the threshold is exceeded. Switching back down only happens once the control value falls below the threshold of the running speed by the hysteresis. Without this hysteresis the fan would audibly cycle at every threshold. In addition, the minimum run time per speed and the minimum idle time apply. Switching up to a higher speed always happens immediately; switching down or off only once the minimum run time has elapsed. After switching off, the unit restarts at the earliest after the minimum idle time. A missing enable, an open window, a responding condensate monitor and frost protection, in contrast, take effect immediately, without any minimum time. Input SH specifies a fixed speed by hand and overrides the automatic mode. Input SB and the operating mode limit the speed at the top. The parameter "Speed switching" defines how outputs V1 to V3 behave. Changeover means that only the output of the running speed is set, which is the normal case for a speed selector switch. Stepped means that at speed 3 the outputs V1, V2 and V3 are all set. |
Valve
and fan are not switched at the same time but in a fixed order:
|
The
parameter "Pipe system" defines how the unit is connected
hydraulically:
Which mode applies is decided by input KU in the "Automatic" operating mode. With several units on one 2-pipe circuit this input is best driven by a shared, central changeover, so that one unit does not heat while the neighbouring unit cools. |
Input BA
is the user's manual intervention. It is usually driven by the output
of the same name on the room controller and set there in the control
element or by a switching time:
|
| Condensate
monitor. If input KW responds, this affects only the cooling
mode — heating continues unchanged. Depending on the parameter,
cooling is blocked completely or the speed is limited to 1. Output SR is
set as long as cooling cannot work because of this. Window contact. With an open window the unit is switched off. Optionally frost protection remains active. Frost protection. If the room temperature at input RT falls below the set threshold, the heating valve opens and the fan runs at speed 1 — regardless of the enable, the window contact, the "Off" operating mode and the minimum idle time. Output SR is set while this happens. Without a linked input RT there is no frost protection. |
| Output BT
counts the hours during which the fan has been running. The counter is
stored and survives a restart of the controller. It is written once an
hour so that the storage medium is spared. |
Inputs |
||
| SG |
Control value |
Control value 0 to 100 % of the controller. It determines
the fan speed. The input has to be linked; without a link the block
calculates with 0 and the unit only runs on a manual command. |
| KU |
Heating/cooling |
Optional. 0 selects heating, other than 0 selects cooling.
The input is only evaluated in the automatic operating mode. Not linked:
the unit heats. |
| SH |
Speed manual |
Optional. 0 leaves the speed to the automatic mode, 1 to 3
specify a fixed speed. Higher values are limited to the configured number
of speeds. Not linked: automatic. |
| BA |
Operating mode |
Optional. 0 = automatic, 1 = heating, 2 = cooling,
3 = fan only, 4 = off. Unknown values count as automatic. Not linked:
automatic. |
| RT |
Room temperature |
Optional. Room temperature in °C, used exclusively for
frost protection. Not linked: there is no frost protection, even if it is
switched on. |
| SB |
Speed limit |
Optional. Highest permitted speed, for example at night
because of the noise. The value 0 means no limit. Not linked: no
limit. |
| KW |
Condensate monitor |
Optional. Other than 0 blocks cooling or limits the speed,
depending on the parameter; heating is not affected. The input can be
inverted. Not linked: condensate is never reported. |
| FE |
Window contact |
Optional. Other than 0 counts as an open window, the
behaviour is set by the parameter. The input can be inverted. Not linked:
the window counts as closed. |
| FR |
Enable |
Optional. Other than 0 enables, 0 switches the unit off
immediately — without minimum run time, but with fan overrun. Not linked:
the block counts as enabled. |
Outputs |
||
| VS |
Fan speed |
Running speed as a value: 0 = off, 1 to 3 = speed. During
the valve lead time this is 0, during the overrun it is 1. |
| VH |
Valve heating |
100 as long as the heating valve is to be open, otherwise
0. |
| VK |
Valve cooling |
100 as long as the cooling valve is to be open, otherwise
0. |
| UM |
Changeover valve |
0 = heating, 1 = cooling. In a 2-pipe system it is only
switched once valve and fan have stopped. |
| SS |
Info status |
State as a bit mask: 1 = fan running 2 = heating 4 = cooling 8 = manual operation or operating mode other than automatic 16 = condensate 32 = frost protection active 64 = window open 128 = changeover lock running 256 = valve lead time running 512 = fan overrun running |
| SR |
Fault |
1 as long as a protective function intervenes — cooling
blocked because of condensate, or active frost protection. Which one it
is can be read from the bit mask at output SS. |
| BT |
Operating hours |
Running time of the fan in hours. The value therefore only
changes once an hour. |
| V1 to V3 |
Fan speed 1 to 3 |
One output per speed. The number follows the parameter
"Number of fan speeds"; speeds that do not exist have no output. |
Parameters |
||
| Number of fan speeds |
1 to 3. Determines how many speed outputs the block
has. |
|
| Speed switching |
Changeover: only the output of the running speed is set.
Stepped: all outputs up to the running speed are set. |
|
| Threshold speed 1 to 3 |
Control value in percent from which the respective speed is
used. Typical values: 10, 40 and 70 %. |
|
| Hysteresis |
By this amount the control value has to fall below the
threshold before switching back down. The hysteresis has no effect when
switching up. |
|
| Minimum run time per speed |
A speed stays in place at least this long before switching
down or off. |
|
| Minimum idle time |
After switching off, the unit stays off at least this long
before it starts again. |
|
| Fan overrun |
After the valve has closed, the fan keeps running at the
lowest speed for this long. |
|
| Valve lead time |
In heating mode the valve opens first; only after this time
does the fan start. The time has no effect in cooling mode. |
|
| Pipe system |
4-pipe: separate valves. 2-pipe: one valve, the direction
is given by output UM. |
|
| Changeover lock heating/cooling |
The mode stays in place at least this long after a
change. |
|
| On condensate |
Block cooling, or limit the speed to 1. Heating is not
affected in either case. |
|
| With an open window |
Everything off, or frost protection stays active. |
|
| Frost protection |
Switches frost protection on. It needs input RT. |
|
| Frost protection temperature |
Below this room temperature the unit heats. |
|
| Speed limit when absent |
Highest speed in the presence states absent and holiday.
0 means no limit. |
|
| Invert window contact input |
For contacts that provide a 1 in the closed state. |
|
| Invert condensate monitor input |
For monitors that provide a 1 in the good state. |
|