Inputs
|
AK
|
Active
|
Active. Monitoring is always in effect. Evaluated is
the change from non-zero to 0 (Inactive): it cancels a pending alarm and
the actuator lock once. The next wind or rain value above the threshold
triggers the alarm again. |
WI
|
Wind km/h
|
Wind speed in km/h. |
RE
|
Rain
|
Rain message. If 1 is present at the input, rain is
detected. Only evaluated when the setting "Rain
safety" in the control element is set to Active. |
AL
|
Alarm
|
If the wind speed exceeds the configured
limit or, with rain safety activated, rain is detected, the
alarm output is set. When the wind drops to the release threshold or
below, the release delay starts; further wind values below the
threshold do not restart it. While the wind is between release and
alarm threshold, the alarm remains and a running delay is
discarded. |
AS
|
Actuator lock
|
If the alarm is triggered by wind or rain, first
the configured safety position is sent to all height and slat outputs
and after a delay time the
actuator lock is activated. |
H1
|
Height percent |
Setpoint height and slat.
If the alarm is active, the configured safety position for height
and slat is output every 10 seconds. |
L1
|
Slat percent |
Parameters
|
|
Number of outputs |
Number of outputs for height and slat. |
|
Delay actuator lock |
If the alarm is triggered by wind or rain, first
the configured safety position is sent to all height and slat outputs
and after this time the actuator lock is
activated. This time should therefore always be greater than the
travel time height of the blind. |