| S1 |
Temp. collector 1 |
Temperature collector field 1. Must be linked. |
| S2 |
Temp. collector 2 |
Optional. Temperature of collector array 2. Not linked: pump P2 stays off, the block works with one array. |
| WP |
Temp. exchanger primary |
Flow of the heat exchanger (solar side). Determines
the diverter valve and the speed of the exchanger pump. Must be
linked. |
| WS |
Temp. exchanger secondary |
Optional. Exchanger flow (buffer side), only shown in the status text. Not linked: the status text shows the primary flow only. |
| PU |
Temp. buffer bottom |
Must be linked. |
| PO |
Temp. buffer top |
Must be linked. |
| SP |
Lock (manual) |
Optional. Not equal to 0 locks: all outputs go to 0 once, then the block sends nothing more (manual mode). Changing to 0 releases, the block evaluates immediately. Not linked: never locked. |
| P1 / A1 |
Pump collector 1 |
On/off or speed 0-100 %. |
| P2 / A2 |
Pump collector 2 |
On/off or speed 0-100 %. |
| PT / AT |
Pump exchanger/buffer |
Secondary pump on/off or speed 0-100 %. |
| VU |
Diverter valve |
0 = buffer top, 1 = buffer bottom. |
| ST |
Status text |
State as plain text, e.g. "laedt oben: K1 64%,
K2 0%, Tauscher 70% (58.2/52.0 C)" (German text). For a text
address (14 byte). |
|
Collector maximum |
Above this temperature the pump of the field stays
off (stagnation protection). Default 120 °C. |
|
Buffer maximum |
If both buffer sensors are above this, charging
stops. Default 85 °C. |
|
Switch-on difference |
Collector versus the colder buffer sensor, above
which the pump starts; also the threshold of the diverter valve.
Default 10 K. |
|
Switch-off difference |
Below this the pump switches off. Limited to the
switch-on difference. Default 5 K. |
|
Gain |
Speed in % per Kelvin of difference. Default
4 %/K. |
|
Minimum speed |
Lower limit of a running pump. Default
12 %. |
|
Switch-over delay bottom |
How long the exchanger flow must be too cold for
the top before the valve switches to the bottom. Default
15 s. |