| TO |
Storage temperature top |
Must be linked. If the sensor is missing or
outside -50 to 150 °C, charging does not take place (fault
in the status text). |
| TU |
Storage temperature bottom |
Optional. Condition for ending charging. Not linked or outside -50 to 150 °C: the top sensor applies. |
| SE |
Setpoint on (top) |
Optional. Switch-on threshold at the top sensor. Not linked or 0: parameter Setpoint on applies. |
| SA |
Setpoint off (bottom) |
Optional. The bottom sensor must reach this temperature for charging to end. Not linked or 0: parameter Setpoint off applies. |
| VL |
Flow temperature generator |
Optional. Releases the charging pump only once the flow is warmer than the storage bottom by the pump switch-on difference. Not linked: the pump runs during the whole charge. |
| SP |
Lock |
Optional. Not equal to 0 locks: no request, pump off, times reset. 0 releases. Not linked: never locked. |
| AN |
Heat request |
1 during charging. |
| AT |
Request temperature |
Setpoint off + request boost during
charging, otherwise 0. If the output is connected to a heat
request, leave the boost there at 0, otherwise it counts
twice. |
| PU |
Charging pump |
On/off. |
| RZ |
Remaining time charge/pause |
Seconds until the end of the maximum charging
time or the pause. 0 without limit. |
| ST |
Status text |
State as plain text. For a text address (14
byte). |
|
Setpoint on / Setpoint off |
Fallback values as long as SE or SA are not
linked. Default 55 °C or 45 °C. |
|
Hysteresis |
Switching gap around both setpoints. Default
0 K. |
|
Maximum charging time |
In minutes, then a pause of the same duration. 0 =
unlimited. |
|
Request boost |
Addition to setpoint off for output AT. Default
0 K. |
|
Pump switch-on difference |
Flow versus storage bottom, above which the
charging pump runs; switches off at half that difference.
Default 5 K. |