Übersicht Jalousie digital

This function block is used to implement a blind control. Please note that the positions can only be determined approximately, a drifting apart between target and actual values cannot always be avoided.


Inputs

LZ
Long distance 
At 0, the blind moves all the way up, at 1 all the way down.
KZ
Short distance
At 0 the blind moves up for a short time, at 1 a short time down. This function is used to adjust the slat.
SH
Setpoint Height
Setpoint height in percent.
SL
Setpoint Lamella Setpoint slat in percent.

Outputs

AU
Up
Output up
AB
Down
Output down
RH
Feedback Height
Feedback current height
RL
Lamella feedback
Feedback current lamella

Parameter

Driving time Height
Time from top to bottom. The position is calculated from this time.
Driving time Lamella Time of the slat from fully closed to fully open. The position is calculated from this time.
Driving time short Time when input KZ Kurzeit is activated to adjust the slat step by step.
Passed over in percent
If the blind is moved all the way up or down, the corresponding outputs are activated longer than necessary to keep the blind open / closed. This overrun is given as a percentage of the height movement time.


See also general parameters of all function blocks.