BA
|
Operating mode*
|
Operating mode:
|
MA
|
Manual button
|
On a rising edge the hot water is heated once
to the setpoint. After the setpoint is reached the input
switches back to 0 if an address has been connected, so that
the address can be connected to a button that switches itself
off again automatically. On a falling edge the heating is
interrupted again.
|
| PU |
Surplus* |
PV surplus. |
IW
|
Actual value*
|
Actual hot water temperature |
| SP |
Setpoint PV* |
Hot water setpoint in automatic mode |
| SM |
Setpoint grid* |
Setpoint when hot water is generated without PV
surplus (manual on or 1x heating) |
| FG |
Enable |
Optional enable. If this input is not
connected, the control is always enabled, otherwise only when
the input is 1. This input can be used when another consumer
should have priority without having to switch the operating
mode. |
| SE |
Setpoint continuous on % |
Optional setpoint when operating mode On or 1x
heating is active. If this input is not connected, 100% is
always output. |
| TM |
Minimum temperature |
Optional minimum temperature. If the value is
greater than 0, it is evaluated as the minimum temperature with
a hysteresis of 1 degree. If the actual temperature drops
below this value, the hot water is kept at this temperature
with grid power as well, independently of the PV surplus and
independently of the operating mode. The heating switches off
again as soon as the actual temperature exceeds the minimum
value by 1 degree. The input Setpoint continuous on % is
used as the setpoint in percent (100% if not connected). If the
input is not connected or 0, the function is disabled. |
SW
|
Setpoint percent
|
Setpoint 0-100% |
| MA |
Manual active |
Info 1x heating manually active |
| RA |
PV control active |
Output is 1 when the control is active or the
time from the parameter Surplus minimum time is reached. |
|
Hysteresis
|
Hysteresis for the setpoint/actual value
comparison. The hysteresis acts in the negative direction, that
means when the actual value is lower than the setpoint minus
hysteresis the heating is switched on, and when the actual value
exceeds the setpoint the heating is switched off. |
|
Gain
|
Speed of the control; with a higher value
the output reacts faster to a change at the input.
A value of 0.4 is recommended for the input in kW.
|
|
Surplus minimum |
Minimum surplus that must at least be present
so that the control starts. If the feed-in falls below this
surplus the control automatically reduces; a surplus should
therefore always be specified so that the control reduces
early. |
|
Surplus [kW] when PU
|
- Positive, surplus is present when the value at the
PU input is positive.
- Negative, surplus is present when the value at the
PU input is negative.
|
|
Surplus minimum time |
Time during which the PV surplus must be present
so that the control starts. This can ensure that PV surplus is
reliably present, for example so that the control does not
constantly start/stop during cloud breaks or load changes. |