| BO |
Temp. boiler |
Temperature boiler. |
PU
|
Temp. buffer
|
Temperature buffer. |
SO
|
Temp. solar
|
Temperature solar (collector).
|
PU
|
Pump
digital
|
Pump digital on/off. |
PA
|
Pump
analog 0-100%
|
Pump analog. As an alternative to
control via switching hysteresis, a pump with
analog control can be used at this output.
|
| VP |
Valve buffer |
Valve switchover boiler/buffer: 1 = buffer, 0 = boiler. |
|
Solar
maximum
|
Maximum temperature solar. If the
temperature exceeds this value, the pump is switched off even if the
storage tank temperature has not been reached. |
|
Boiler maximum |
Switch-off temperature boiler. If the boiler temperature exceeds this
value, boiler charging is ended. |
|
Buffer maximum |
Switch-off temperature buffer. If the buffer temperature exceeds this
value, buffer charging is ended. |
|
Hysteresis
solar on
|
Difference between solar and storage tank
at which the control becomes active.
|
|
Hysteresis
solar off
|
Difference between solar and storage tank
at which the control becomes inactive. |
|
Gain |
Control setting; the higher the value, the faster the
analog output changes with a change in temperature. |
|
Boiler priority |
If this parameter is active, the boiler is charged first. Only
once the boiler maximum is reached is switching to buffer charging
performed. |