KEBA charging station| With this function block the KEBA charging station is controlled so that only the PV surplus is charged. |
Inputs |
||
| BA |
Operating mode* |
Operating mode:
|
| LM |
Charging current
manual A |
Charging current setpoint for operating mode manual |
| PU |
Surplus* |
PV surplus. The input must not be limited to 0; both positive and negative values must arrive at the input so that the control can react correctly. With the parameter Type of surplus it can be set whether positive or negative means surplus. |
| FG | Enable | Optional enable. If the input is 1, the control is enabled.
This input can be used to switch the control in
automatic mode on and off without having to change the operating
mode. If the input is not connected, the control is always enabled. |
| LE | Session kWh setpoint | Charging energy for the current charging session. With a value > 0 charging is stopped when the energy has been charged. After the stop this input is reset to 0. |
| AN | Charging current minimum | Optional input for charging current minimum. If this input is not connected, the charging current is limited from the parameters. |
| AH | Charging current maximum | Optional input for charging current maximum. If this input is not connected, the charging current is limited from the parameters. |
Outputs |
||
| ER |
Communication
error |
Communication error |
| SS | Status plug |
0 unplugged 1 plugged on charging station 3 plugged on charging station plug locked 5 plugged on charging station plugged on EV 7 plugged on charging station plug locked plugged on EV |
| SL | Status charging |
0 starting 1 not ready for charging; e.g. unplugged, X1 or "ena" not enabled, RFID not enabled 2 ready for charging; waiting for EV charging request (S2) 3 charging 4 error 5 authorization rejected |
| LA | Power W | Current charging power in W |
| AA | Session kWh current | Energy charged in the current charging session |
| FU | Enable surplus charging | Output is 1 when the control is active. |
| LS | Charging current setpoint A | Setpoint that is sent to the charging station. |
| LR | Charging current setpoint A status | Feedback charging current. The feedback may differ from the setpoint if, for example, the minimum set charging current is undershot. |
Parameters |
||
| IP
address |
IP address of the charging station | |
| Gain
P |
Speed of the control; with a higher value the output reacts faster to a change at the input. | |
| Minimum surplus | Minimum surplus that must at least be present so that the control begins. | |
| Charging current
minimum |
Minimum charging current |
|
| Charging current maximum |
Maximum charging current | |
| Type of surplus |
|
|
| Start at surplus | Minimum surplus at which the control starts. Value is always positive. | |
| Control time on | Time for control on. The surplus must be above "Start at surplus" for at least this time so that the control starts. | |
| Control time off | Time for control off. If the surplus is below "Surplus minimum" for this time, the control is switched off. | |
| Surplus minimum | The control regulates to this value; this surplus always remains. Value is always positive. | |