FG
|
Enable
|
Enable.
At 1 the value is sent cyclically. This input is optional; if nothing is
linked to the input, the block is enabled automatically.
|
TM
|
Time
|
Time interval for the cyclic sending in
seconds. This input is optional; if nothing is linked to the input, it
is sent every 5 seconds. The minimum time is 1 second.
|
SW
|
Setpoint
|
Value that is sent cyclically.
|
A1
|
Variable
|
Variable. A variable from the KNX range must be linked to the output.
|
TM
|
Remaining time
|
Remaining time in seconds until the next send.
|
|
Apply changes
|
If this parameter is activated, a
change of the value at input SW is sent immediately and the
cycle time is restarted. Default: activated.
|