KNX Time Server| This function block cyclically sends the current time to the KNX bus. For example for KNX devices that have no real-time clock. The controller synchronizes the time cyclically with a time server on the Internet, so it is always up to date. In addition to the KNX data types Time and Date, time and date are also output as individual outputs. |
Inputs |
||
Outputs |
||
| ZT |
Time |
Variable for the time, this must
be of type "EIS 3 Time". |
| DT |
Date |
Variable for the date, this must be of type "EIS 4 Date". |
| ZS |
Hour |
Time hour |
| ZM |
Minute |
Time minute |
| ZS |
Second |
Time second |
| DD |
Day |
Date day |
| DM |
Month |
Date month |
| DJ |
Year |
Date year |
| DP | DPT19001 | Output for 8 byte DPT19001 data type. If this output is used, a variable of type EIS16 8 byte counter value without sign must be connected. |
Parameters |
||
| Send
cyclically |
Time at which date and time are
sent cyclically to the bus; at 0 they are only sent on
change. This time refers only to the outputs ZT
and DT, the remaining outputs are not sent cyclically. |
|