FG
|
Enable
|
Enable. At 1 the mixer is
enabled and the outputs are driven. At 0 the
mixer closes for the run time and then switches off all outputs. If the
input is not assigned, the mixer is automatically enabled.
|
SV
|
Setpoint
flow*
|
Flow setpoint to which control is
performed.
|
| SR |
Setpoint return flow* |
Return flow limitation. If the return flow temperature exceeds this value,
control is regulated back. |
IV
|
Actual value
flow*
|
Flow actual value.
|
| IR |
Actual value return flow* |
Return flow actual value. |
AU
|
Open
|
Output mixer open.
|
ZU
|
Close
|
Output mixer close. |
PR
|
Percent
|
0-100% output. For mixers with
analog input. The manipulated variable of the internal controller IY is added to or subtracted from this
value depending on the operating mode. The accumulation
is performed at every rising edge at the open/close outputs;
using the gain parameter and the PWM
settings the control time can thus be influenced. If the
percent output is used, the P component must be set significantly smaller than the
default value.
|
PU
|
Pump
|
Pump. A heating circuit pump can be
connected here. It is switched on together with the enable.
|
ST
|
Info
Status
|
Output is set to 1 when the
mixer is active.
|
IY
|
Info
Y
|
Output of the internal controller for
diagnostic purposes. The output ranges from -255 (whole PWM time close) to
+255 (whole PWM time open). |
IP
|
Info
PWM
|
Output of the internal PWM timer -
time until next open/close cycle.
|
|
Run time
|
Run time of the mixer. If the
enable is switched off, the mixer closes for 2x the mixer run time.
|
|
Gain
|
Gain for the internal controller.
With a higher value the mixer reacts faster. Important: With
too high a value the mixer starts to oscillate (constant
open/close control).
|
|
PWM time
|
Time for one open/close cycle. The
manipulated variable from 0-255 is mapped to this time. On time
is PWM time/255 * manipulated variable. This time also determines when the
manipulated variable is integrated (time +/- percent output).
|
|
PWM min. pause
|
In this parameter a minimal pause time can optionally
be set (both outputs remain
off). This pause is observed at minimum, even if the
calculated off time would be shorter. After an open cycle the
pause should be at least as long as the flow sensor needs
to report back the current temperature.
|
|
PWM max. pulse
|
In this parameter a
maximal pulse time can be set. The internal controller is limited to
this maximum (maximal time for open), even if the
calculated on time would be larger.
|
|
Hysteresis
|
Within this hysteresis the
temperature is considered reached and the mixer remains in its current
position. The hysteresis acts in both directions,
for example with a hysteresis of 1 the temperature
is considered reached within +/- 1 degree.
|
|
Anti-blocking function |
With this parameter the mixer is started 1x per week when
the enable is 0. This is intended to prevent the mixer from
blocking when it is not in operation for too long. The function
is started on Sunday at 0:00h. The mixer travels the
mixer run time open/close, or the analog output is set to 0/100 percent,
and the pump output is switched on.
When the anti-blocking function is active, 100 +
step is output at the Status output.
- 101: Outputs off
- 102: Mixer open
- 103: Wait time mixer run time
- 104: Mixer close
- 105: Wait time mixer run time
- 106: Pump on
- 107: Wait time mixer run time
- 108: Outputs off, cycle finished.
|