| LB |
On/off |
Switches the light on (1) and off (0). |
| LP |
Percent |
Brightness in percent from 0 to 100. The value is sent to the device on every change. |
| SB |
Status on/off |
Feedback whether the light is switched on. |
| SP |
Status percent |
Feedback of the set brightness in percent. |
| S1 |
Status switch 1 |
State of the push-button or switch 1 connected to the device. |
| S2 |
Status switch 2 |
State of the push-button or switch 2 connected to the device. |
| AI |
Addon analogue input |
Voltage at the analogue input of the addon. Only present when the addon is enabled. |
| DI |
Addon digital input |
State of the digital input of the addon. Only present when the addon is enabled. |
| T1 |
Addon temperature 1 |
Temperature of the first DS18B20 sensor, or of the DHT22 if that one is selected. Only present when the addon is enabled. |
| T2 |
Addon temperature 2 |
Temperature of the second DS18B20 sensor. Only with the setting "+Addon DS18B20". |
| T3 |
Addon temperature 3 |
Temperature of the third DS18B20 sensor. Only with the setting "+Addon DS18B20". |
| F1 |
Addon humidity in % |
Relative humidity of the DHT22 sensor. Only with the setting "+Addon DHT22"; the output then takes the place of T2. |
|
MQTT topic |
Topic of the device, exactly as in the MQTT settings of the device. Example: shellyddimmerg3-AABBCCDDEEFF |
|
Addon |