Overview Staircase delay

This function block implements a so-called "staircase function", for example a staircase or corridor light with two switches at the beginning and end of the staircase / corridor. At the beginning the light is switched on with a pushbutton; after a certain time the light is switched off automatically. Unlike, for example, an off-delay, with this function block the output can also be switched on or off again manually, for example at the end of the corridor.


Inputs

TR
Trigger
Trigger to switch on.
ZT
Time
Time after which the output should switch off again automatically.

Outputs

A1
Output
Output
RZ
Remaining time
Time until switch-off.

Parameters

Time unit
Time unit. With this parameter it is defined how the input ZT time should be interpreted, for example 10 as 10 seconds or 10 minutes.
Trigger
Trigger behavior

  • Rising edge: Output is activated on change from 0 to 1.
  • Falling edge: Output is activated on change from 1 to 0.
  • Change: Output is activated on every change.
  • On KNX telegram: Output is activated on a telegram. For example when a KNX pushbutton can only send 1 and no edge.
  • On KNX telegram 1=on/0=off: Output is activated on a 1 telegram, deactivated on 0 without waiting for the time to elapse, in order to switch off the light manually.