FG
|
Enable
|
Enable.
The controller is enabled when input 1 is applied. This input is
optional; if the input is not connected, the controller is
automatically enabled. |
IW
|
Actual value*
|
Actual value
|
SW
|
Setpoint*
|
Setpoint
|
A1
|
Setpoint
|
Setpoint |
Regulation period
|
Regulation time in seconds. The target/actual comparison is only carried out at this interval.
|
Hysteresis
|
Hysteresis.
|
Hysteresis Typ
|
With this parameter the hysteresis can be set.
- plus/minus: IW < SW - hysteresis = on,IW > SW + hysteresis = off
- minus: IW < SW - Hysteresis = on,IW > SW = off
- plus: IW < SW = on,IW > SW + hysteresis = off
|
|
|