Übersicht Two-point controller

This function block is used to implement a two-point controller. 


Inputs

FG
Enable
Enable. The controller is enabled when input 1 is applied. This input is optional; if the input is not connected, the controller is automatically enabled.
IW
Actual value*
Actual value
SW
Setpoint*
Setpoint

Outputs

A1
Setpoint Setpoint

Parameter

Regulation period
Regulation time in seconds. The target/actual comparison is only carried out at this interval.
Hysteresis
Hysteresis.
Hysteresis Typ
With this parameter the hysteresis can be set.

  • plus/minus: IW < SW - hysteresis = on,IW > SW + hysteresis = off
  • minus: IW < SW - Hysteresis = on,IW > SW = off
  • plus: IW < SW = on,IW > SW + hysteresis = off





See also general parameters of all function blocks.