Block Energy
Monitor| This
control element provides
the energy flow display. This control element is linked to the corresponding logic block, see function block Structured Block Energy Monitor. The variables are linked here to the function block. First create the corresponding function block and link the variables, then right-click on the control element and select the function block to link the control element. |
The current PV power (Production), the grid power (Net), the Consumption and the Autarky are displayed. If the battery indicator is enabled, the state of charge and the state of the storage (Load, Discharge, Standby) are shown additionally. Up to five consumers can be displayed with their own labelling.
Note on older recordings. The recording has been reworked. Values from before that remain complete, but sit one hour further to the right in the chart than the new ones; for the state of charge and for autarky they hold the hourly maximum instead of the middle between minimum and maximum. At the changeover point an offset is therefore visible. In addition the energy values were booked too high whenever a power changed during the hour.
Clicking on the control element shows the dialog with the energy evaluation. In the overview the total values Autarky, Production, Consumption, Import, Export, Savings and Yield are displayed. The icon at the top right switches between overview and detail view. The button in the middle selects the time range:
Display |
|
| Background | Background color |
| Font | Font color |
| ID | Identifier for assigning the control element to the Energy Monitor function block. |
| Battery indicator | Determines whether the display of the battery storage (state of charge, charge/discharge state) is shown. |
Display consumer |
|
| Text consumer 1 … 5 | Labelling of the up to five displayed consumers. Line breaks can be inserted with the special character "\n". |
Connected variablessee function block Structured Block Energy Monitor |
|
| Net power kW | Current grid power (positive = consumption, negative = feed-in). |
| PV power kW | Current power of the photovoltaic system. |
| Consumption kW | Current total consumption. |
| Battery power kW | Current charge/discharge power of the battery storage. |
| Battery charge % | State of charge of the battery storage in percent. |
| Battery status | State of the battery storage (charge, discharge, standby). |
| Autarky % | Current autarky in percent. |
| Display consumer 1 … 5 | Current power of the up to five individual consumers. |