Block Ventilation| This
block controls a mechanical ventilation system with heat recovery on
demand, based on the CO2 level and the humidity. It provides the fan
stage both as individual bits and as a value, switches the bypass for
summer cooling, releases the pre-heater for frost protection, counts
the operating hours and reports when the filter is due for
replacement. Occupancy is taken from the Block Presence block, as with every block element; input AB acts in addition. See also Presence in general. The matching control element is Block Ventilation. It is used to set the base stage per occupancy state, the switching times and the filter interval; the block must be linked to the control element. For a single extract fan in a toilet or bathroom, use the block Block Exhaust air. |
The
stage that is actually run is always the highest of all demands.
This is simple, easy to follow and covers practical requirements.
Demand comes from:
Hysteresis: When stepping up, the threshold itself applies; when stepping down, the threshold minus the hysteresis. Without hysteresis the system would oscillate at every threshold. Minimum run time: A higher demand takes effect immediately. Stepping down only happens once the current stage has reached its minimum run time. This keeps the system from cycling at the threshold. |
| If the
indoor humidity rises above the value "Humidity protection from", at
least the configured stage is run. However, this only happens if the outdoor air is absolutely drier than the indoor air. To determine this, the block calculates the absolute humidity in g/m³ from inputs RF/TI and RA/TA. If the outdoor air is more humid, ventilating would raise the humidity in the room instead of lowering it - humidity protection then does not take effect. In summer this is the normal case: 70 % at 28 °C outdoors contains considerably more water than 70 % at 22 °C indoors. If inputs RA or TA are not linked the comparison cannot be made; humidity protection then always takes effect. |
| The
bypass routes the supply air past the heat exchanger and
therefore cools in summer. It only opens when all conditions are met at
the same time: the outdoor temperature is above the release threshold,
the indoor temperature is at least the configured difference above the
outdoor temperature, and there is a cooling demand (indoor temperature
above the configured threshold). In addition the system must be
running, that is, at least stage 1 must be active. The pre-heater protects the heat exchanger against icing up. It is released as soon as the outdoor temperature falls below the configured limit, and switched off again once the temperature exceeds that limit by the hysteresis. While frost protection is active the bypass always stays closed. |
| The
block counts the time during which a stage greater than 0 is run and
outputs it at output BT in hours. The counter value is stored on the
controller and survives a restart. The maintenance interval is set in the control element in operating hours, not at the block - this way the user can also change it in the APP. Once it is reached, output FW goes to 1. Acknowledgement is done either with a rising edge at input QU or with the button in the control element; the counter then starts again from zero. The value 0 switches filter maintenance off. |
Inputs |
||
| CO |
CO2 |
CO2 level of the room air in ppm. If the input is not
linked or the CO2 evaluation is switched off, this demand does not
apply. |
| RF |
Humidity indoors |
Relative humidity in the room in %. Basis for the humidity
stages and for humidity protection. |
| RA |
Humidity outdoors |
Relative humidity of the outdoor air in %. Needed together
with TI and TA to compare the absolute humidity. |
| TI |
Temperature indoors |
Room temperature in °C. Basis for the cooling demand of
the bypass and for the humidity comparison. |
| TA |
Temperature outdoors |
Outdoor temperature in °C. Basis for the bypass and for
frost protection. |
| SV |
Set stage |
0 = automatic (no manual setting), 1 to 4 =
fixed stage, 5 = switched off by hand. The manual setting overrides the demand, it does not merely cap it: only this way can the system be switched off by hand while CO2 or humidity are still requesting. It takes effect immediately, without waiting for the minimum run time. The control element and the switching times both operate through this address - a switching time can therefore force a fixed stage and hand the system back to automatic later. |
| PA |
Boost ventilation |
A rising edge starts boost ventilation: at least the
configured stage is run for the configured run-on time. |
| AB |
Absent |
1 = nobody at home; the base stage of the state "Absent"
applies. The input acts in addition to the central occupancy state and
therefore only needs to be linked if absence is to come from a different
source. |
| BA |
Operating mode |
Operating mode 0 to 4. If the input is linked, the
corresponding parameter "Base stage operating mode x" sets the base stage
and takes precedence over the setting in the control element. |
| FE |
Window open |
1 = a window is open. What happens then is defined by the
parameter "Behaviour with window open". |
| SP |
Lock |
1 = the system goes to stage 0 and stays there as long as
the input is set. |
| QU |
Acknowledge filter |
A rising edge resets the operating hours counter to zero
and thereby clears the filter message. |
Outputs |
||
| S0 |
Stage 0 |
1 when the system is stopped. |
| S1 to S4 |
Stage 1 to 4 |
Exactly one of these outputs is set. All outputs are
always present; stages above the configured number of stages remain
permanently 0. |
| SW |
Stage as value |
The current stage as a value from 0 to 100 %, relative to
the configured number of stages. With three stages this gives 0, 33, 67
and 100 %. For ventilation units with a continuous input. |
| BY |
Bypass |
1 = bypass open (summer cooling). |
| VH |
Pre-heater |
1 = frost protection active, the pre-heater is
released. |
| FW |
Filter maintenance due |
1 = the configured maintenance interval has been
reached. |
| BT |
Operating hours |
Operating hours since the last acknowledgement. |
| ST |
Info status |
Status value for the visualisation. The bits are added
up: 1 = CO2 is requesting 2 = humidity is requesting 4 = humidity protection active 8 = boost ventilation running 16 = manual setting active 32 = window open 64 = locked 128 = bypass open 256 = frost protection active 512 = filter maintenance due |
Parameters |
||
| Number of stages |
Number of fan stages, 2 to 4. Outputs S0 to S4 are always
present regardless of this setting. |
|
| Evaluate CO2 |
Switches the demand based on CO2 on or off. |
|
| CO2 threshold stage 1 to 4 |
CO2 level in ppm at which the respective stage is run.
Typical values: 800, 1000, 1200 and 1500 ppm. |
|
| CO2 hysteresis |
The value has to fall below the threshold by this amount
before the stage is reduced. |
|
| Evaluate humidity |
Switches the demand based on the indoor humidity on or
off. |
|
| Humidity threshold stage 1 to 4 |
Relative indoor humidity in % at which the respective
stage is run. |
|
| Humidity hysteresis |
Like the CO2 hysteresis, applied to the humidity. |
|
| Humidity protection from |
From this indoor humidity onwards at least the humidity
protection stage is run - but only if the outdoor air is absolutely
drier. |
|
| Humidity protection minimum stage |
Stage that humidity protection requests as a minimum. |
|
| Base stage operating mode 0 to 4 |
Base stage per value at input BA. Only evaluated if BA is
linked. |
|
| Boost ventilation stage |
Stage that is run as a minimum during boost
ventilation. |
|
| Boost ventilation run-on time |
Duration of boost ventilation in minutes. |
|
| Behaviour with window open |
No change, reduce by one stage, fall back to the base
stage, or switch off completely. |
|
| Minimum run time per stage |
A stage stays active at least this long before it is
reduced. A higher demand takes effect immediately. |
|
| Bypass active |
Releases the bypass control. |
|
| Bypass release from outdoor temperature |
Below this outdoor temperature the bypass stays closed. |
|
| Bypass minimum difference indoors-outdoors |
This much cooler it has to be outside for the bypass to
achieve anything at all. |
|
| Bypass cooling demand from indoor
temperature |
Only above this room temperature is there a cooling
demand. |
|
| Bypass hysteresis |
The conditions have to fall short by this amount before
the bypass closes again. |
|
| Pre-heater active |
Releases frost protection. |
|
| Frost protection from outdoor temperature |
Below this outdoor temperature the pre-heater is
released. |
|
| Frost protection hysteresis |
The outdoor temperature has to rise by this amount again
before the pre-heater is switched off. |
|