Block Roller shutter/blind
Safety| This
control element operates
Blind Safety. The control element is connected to the corresponding logic block, see function block Structured Block Blind Safety. See also Presence in general. First create the corresponding function block and connect the variables, right-click on the control element and select the function block to connect the control element. Clicking on the control element shows a dialog in which the safety can be activated/deactivated. The settings can be changed by clicking on the gear icon in the title bar: Wind alarm above: Wind speed (kmh) from which the alarm is triggered. Wind enable below: Wind speed (kmh) below which the alarm is enabled again. Safety rain: Activates or deactivates the evaluation of the rain input. If the setting is Active, a rain message also triggers the alarm. Delay: Time after which the actuator lock is released again after enabling. Position H/S: Height and slat (0 – 100%) that are approached when safety is active (wind or rain). |
Display |
|
| View | View of the control element, Block, Basic Screen. |
| Text | Text to be displayed. The size of the
text is automatically scaled with the control element. Line breaks
can be inserted with the special character "\n", for example
"Line1\nLine2"; a maximum of two lines is possible. |
Connected variables
Connections are made at the function block. |
|