Block Meter This function block keeps one meter – for electricity, water, heat, cooling, gas, oil, pellets or a unit of your own. From the meter value it derives the consumption of today, yesterday, the week, the month and the year together with the previous period, optionally calculates the costs, records every hour and monitors the consumption. For water it also protects against leaks and pipe bursts and can close a shut-off valve.
The meter value can come from any bus: KNX, Modbus, M-Bus, MQTT, a pulse input or an internal connection. The block is operated with the control element Block Meter: consumption, history, log, settings, acknowledge and meter reading. The block itself only holds the commissioning data.
| Meter reading | The increase is formed according to the input type. For an absolute meter reading: a small decrease (below 10 %) is noise and is ignored, a jump back near the overflow value is counted on, a large decrease means the meter was replaced or reset – nothing is counted and the new value becomes the new base. A jump upwards that would mean more than the highest flow is discarded. All of this is written to the log. The block's own meter reading always continues. |
| Periods | Today, week (from Monday), month and year in local time. The previous value (yesterday, previous week, month, year) only counts if the stored period is exactly the preceding one. |
| Costs | Each increase is valued at the price valid at that moment, the base fee is spread over the hours. By default the tariffs of the project (location, e.g. from the import of the GDAS Manager) are used: the block takes the valid tariff of its medium with unit, VAT, base fee and the price steps per time of day, for water optionally including waste water; a new tariff applies from its start. Without a matching tariff, or for an exchange-based tariff, the own prices of the control element apply (single tariff or peak/off-peak); a new own price applies from the moment it is saved. Costs recorded so far always remain. Gas is billed per kWh (kWh = m³ × correction factor × calorific value), unless the project tariff states m³. Costs are shown in the currency of the project. |
| Recording hourly |
Consumption, feed-in, meter reading, costs, energy and peak flow per hour. The control element requests them aggregated per day, week, month and year. The data is kept for about ten years. |
| Monitoring | Daily limit, deviation from the mean of the last 14 days, continuous consumption at night and meter failure. Set in the control element. |
| Water protection | A draw-off starts with the first increase and ends when the meter has counted nothing for an adjustable idle time. Checked are the volume and duration per draw-off (separately for present and absent), the flow over a minimum time and the leak sensors. For each rule you choose whether it only reports or closes the valve. The absent profile applies in the house modes absent and holiday, optionally also after a long time without any draw-off. |
The valve only opens deliberately: by acknowledging in the control element or with a rising edge at input QU – never by itself and not after a restart either. If a leak sensor is still active, it stays closed. After a restart the block sends the stored state of the valve.
Leak sensors act immediately, even during the startup delay. The consumption rules only start afterwards.
| ZS | Meter reading | The meter value, depending on the parameter input type as meter reading, pulse, flow or power, or difference value. Pulses and difference values on an address are counted per telegram – even if the meter sends the same value for every pulse. |
| ZE | Meter reading feed-in | Second meter for the feed-in, only with the parameter import and feed-in. Same input type and factor. |
| DF | Flow / power | Optional. Measured flow or power for display and water protection. Without this input the value is estimated from the interval between the last increases. |
| L1 – L4 | Leak sensor | 1 = water detected. Only for the medium water. |
| VR | Valve feedback | Optional, 1 = valve closed. If it does not match the command after the set waiting time, the block reports a fault. |
| HT | Peak tariff | 1 = peak tariff, only with the setting peak/off-peak via input. |
| GE | Allow large draw-off | While 1, at most 72 hours, volume and duration per draw-off are not checked, e.g. when filling a pool. Flow and leak sensors stay active. |
| QU | Acknowledge | Rising edge: reset the messages and open the valve. |
| ZS | Meter reading | Meter reading of the block in the base unit of the medium (electricity, heat, cooling kWh; water and gas m³; oil l; pellets kg). |
| LE | Flow / power | Base unit per hour (kW, m³/h ...). Sent on a change above 5 %, at most every 10 seconds. |
| HE, GE, MO, JA | Today, yesterday, month, year | Consumption of the period. |
| KH, KM | Costs today, costs month | Only with costs switched on. |
| VZ | Valve closed | Control of the shut-off valve, polarity set with the parameter valve. |
| AL | Alarm | 1 as long as a rule has triggered and has not been acknowledged, and during the test mode. |
| SF | Fault | The meter no longer sends or the valve feedback does not match. |
| ST | Info status | Bit mask: 1 alarm, 2 valve closed, 4 volume, 8 duration, 16 flow, 32 night, 64 leak sensor, 128 daily limit, 256 deviation, 512 meter not sending, 1024 valve feedback, 2048 test mode, 4096 large draw-off, 8192 profile absent, 16384 learning phase, 32768 startup delay. |
The meter values are sent once per minute, alarm, valve and status immediately.
| Medium | Electricity, water, heat, cooling, gas, oil, pellets or other. Unit, symbol and the functions of the control element depend on it. |
| Input type | Meter reading, pulses (each pulse counts the factor), flow or power (summed up every second) or difference values (each value is the increase since the last one). |
| Factor | Input value × factor = amount in the base unit. For pulses the amount per pulse, e.g. 1 litre per pulse = 0.001 m³. If an electricity meter delivers Wh, the factor is 0.001. |
| Import and feed-in | A second meter at input ZE, only for electricity, heat and cooling. |
| Overflow value | Highest reading of the meter after the factor, after which it starts again at 0 (e.g. 99999). 0 = no overflow. |
| Highest flow / power | Plausibility: increases that would mean more than this value are discarded. 0 = no check. |
| Startup delay | For this time after the start the consumption rules do not evaluate. Default 30 s. |
| Push message, page | A push message to the APP on every trigger, optionally with the page that opens when it is tapped. |
| Valve | VZ = 1 closes (default) or VZ = 0 closes. |
| Unit | Unit of the amount for the medium other. |
| Flow factor | Input DF × factor = base unit per hour, e.g. l/min to m³/h = 0.06. |
| Diagnostics | Writes hour closing, draw-offs and meter events to the log of the controller. |
A right-click on the block leads via Go to linked element directly to the control element.