Block Room Controller| Block function block for
the control element Block
Room Controller; the control element must be connected to this
function block. See
Block Presence and Presence
General. Alternatively, this room controller can also be used without the Block control element. Therefore, inputs for operating mode, Standby and Night are also available. These can, for example, also be controlled from a KNX room controller. |
The controller always operates in
one mode only, either heating or cooling. Switchover happens
automatically via the enable inputs and the switchover thresholds:
Hysteresis switchover cooling mode: The hysteresis raises the switch-on threshold of the cooling mode. With the default value 0, the controller switches to cooling mode as soon as the setpoint is exceeded (provided cooling is enabled and operating mode Comfort is active). A larger value (e.g. 2) creates a neutral zone between heating and cooling in which both valves remain closed. If both enables are set at the same time, the room temperature determines the mode: below the setpoint the controller heats, above setpoint + hysteresis it cools. |
Inputs |
||
| BA |
Operating mode |
Operating mode: 1=Comfort 2=Standby 3=Night 4=Frost |
| SK |
Setpoint
Comfort* |
Setpoint Comfort |
| SS | Setpoint Standby | Setpoint Standby. This input is available for compatibility reasons in case the controller is used via external addresses without the Block control element. Block room controllers have no operating mode; operating mode 1 and Setpoint Comfort are always preselected. |
| SN | Setpoint Night | Setpoint Night. This input is available for compatibility reasons in case the controller is used via external addresses without the Block control element. Block room controllers have no operating mode; operating mode 1 and Setpoint Comfort are always preselected. |
| SF | Setpoint Frost | Setpoint Frost. If this input is not connected, 5 degrees is automatically set. |
| BH | Base setpoint heating | Base setpoint heating mode (is added to the setpoint) |
| BK | Base setpoint cooling | Base setpoint cooling mode (is added to the setpoint) |
| FH | Enable heating | Enable heating mode. Optional; if the input is not connected, heating mode is always enabled. |
| FK | Enable cooling | Enable cooling mode. Optional; if the input is not connected, cooling mode is always enabled. See heating / cooling mode sequence. |
| OI | Offset room temperature | Optional offset to the room temperature. This value is added to the input room temperature. This is useful when the correction is to be adjusted via the visualization, so that it does not have to be added via a separate logic. |
| FK | Window contact | Window contact (1=Open) If no variable is connected, the input is ignored, so a variable does not have to be connected. |
| RT | Room temperature* | Room temperature |
Outputs |
||
| VH |
Valve
Heating |
Valve heating |
| VK |
Valve
Cooling |
Valve cooling |
| HK | Valve heating+cooling | Valve heating and cooling (if only one heating/cooling circuit) |
| SO | Info Setpoint | Setpoint (setpoint from operating mode + base setpoint) |
| RY | Info Manipulated variable | Manipulated variable of the internal PI controller. Auxiliary value for better adjustment of the PID controller; value ranges from -255 to +255. |
| UH | Info Switchover heating | Threshold switchover to heating mode |
| UK | Info Switchover cooling | Threshold switchover to cooling mode |
| ST | Info Status | Status bit-coded: Bit 0 = State_Heating Bit 1 = State_Cooling Bit 2 = State_WindowOpen Bit 3 = State_Valve_Heating Bit 4 = State_Valve_Cooling |
Parameters |
||
| Type |
Two-point or continuous with PI controller. Two-point is used for normal valves, continuous for valves with an analog input. | |
| Control time |
Control time |
|
| Gain
P |
Gain for type continuous, proportional component of the controller. | |
| Reset time
I |
Reset time for type continuous, integral component of the controller. | |
| Window contact mode |
|
|
| Invert window contact |
Invert window contact; default 1 = window open, inverted 0 = window open. | |
| Window contact time |
Time until window open is detected (minimum 1 second). | |
| Hysteresis two-point |
Hysteresis of the two-point controller. | |
| Hysteresis switchover cooling mode |
Hysteresis switchover to cooling mode. If the room temperature exceeds setpoint + hysteresis, the system switches to cooling mode (default 0). See heating / cooling mode sequence. | |
| Anti-blocking function | With this option, the outputs for valves are switched to 1 once per week in order to prevent blocking. | |